OLTC.100A On-Load Tap-Changer Tester

The OLTC.100A is a compact and reliable tester designed for the measurement of on-load tap-changers (OLTCs) — the only moving part connected to the transformer circuit. Regular testing of OLTCs is critical, as outlined in the Procedures for Handling and Preventive Tests for Electrical Equipment, which require verification of switching sequence and operation time.

The OLTC.100A is specifically built to measure:

  • Transition waveform

  • Transition time

  • Transient resistance value

  • Three-phase synchronization

It provides high-accuracy data for transformer maintenance, fault detection, and preventive diagnostics.

Function

  • Measures transition resistance, time, and waveform of OLTCs

  • Supports multi-range current outputs for different resistance levels

  • Provides high sampling rate (20 kHz) for accurate waveform capture

  • Local storage for test results and analysis

  • Lightweight and portable with separate host and wire box for convenience

Technical Specifications

Output Current

  • 1.0A

  • 0.5A

  • 0.2A

Measuring Range (Transition Resistance)

  • 0.3Ω – 20Ω (at 1.0A)

  • 5Ω – 40Ω (at 0.5A)

  • 20Ω – 100Ω (at 0.2A)

Transition Time

  • 0 – 320 ms

Open Circuit Voltage

  • 24V

Measurement Accuracy

  • Transition resistance: ±(5% of reading ±0.1Ω)

  • Transition time: ±(0.1% of reading ±0.2 ms)

Sampling Rate

  • 20 kHz

Storage Method

  • Local storage

Dimensions

  • Host: 360 × 290 × 170 mm

  • Wire box: 360 × 290 × 170 mm

Weight

  • Host: 6.15 kg

  • Wire box: 4.55 kg

Conditions of Use

  • Ambient temperature: –10°C to +50°C

  • Ambient humidity: ≤85% RH

  • Power supply: AC 220V ±10%

  • Frequency: 50 ±1 Hz