OLTC.100A On-Load Tap-Changer Tester
The OLTC.100A is a compact and reliable tester designed for the measurement of on-load tap-changers (OLTCs) — the only moving part connected to the transformer circuit. Regular testing of OLTCs is critical, as outlined in the Procedures for Handling and Preventive Tests for Electrical Equipment, which require verification of switching sequence and operation time.
The OLTC.100A is specifically built to measure:
Transition waveform
Transition time
Transient resistance value
Three-phase synchronization
It provides high-accuracy data for transformer maintenance, fault detection, and preventive diagnostics.
Function
-
Measures transition resistance, time, and waveform of OLTCs
-
Supports multi-range current outputs for different resistance levels
-
Provides high sampling rate (20 kHz) for accurate waveform capture
-
Local storage for test results and analysis
-
Lightweight and portable with separate host and wire box for convenience
Technical Specifications
Output Current
-
1.0A
-
0.5A
-
0.2A
Measuring Range (Transition Resistance)
-
0.3Ω – 20Ω (at 1.0A)
-
5Ω – 40Ω (at 0.5A)
-
20Ω – 100Ω (at 0.2A)
Transition Time
-
0 – 320 ms
Open Circuit Voltage
-
24V
Measurement Accuracy
-
Transition resistance: ±(5% of reading ±0.1Ω)
-
Transition time: ±(0.1% of reading ±0.2 ms)
Sampling Rate
-
20 kHz
Storage Method
-
Local storage
Dimensions
-
Host: 360 × 290 × 170 mm
-
Wire box: 360 × 290 × 170 mm
Weight
-
Host: 6.15 kg
-
Wire box: 4.55 kg
Conditions of Use
-
Ambient temperature: –10°C to +50°C
-
Ambient humidity: ≤85% RH
-
Power supply: AC 220V ±10%
-
Frequency: 50 ±1 Hz