top of page
SDR11 HV Discharge Rod
download_edited_edited.png
Introduction to the SDR11 HV Discharge Rod:
  • This instrument will allow you to conduct the safe damp discharge of the residual charge on the cable / equipment by limiting the discharge current.
     

  • Each model features high grade glass fibre tubing and incorporates encapsulated resistor chains.
     

  • It is supplied as standard with earthing wire (10 sq.mmx 5mtr), yellow green wire and carry case.

Features:

  • Safe HV discharge rod for soft damp discharge of cables and / or equipment under test

  • Supplied with flexible cable with heavy duty brass clamp for easy earth connection

  • Robust single pole device

  • No switches

  • Suitable for voltages to 11kV DC

  • Supplied with cushion soft carrying case

Technical Specifications 
  • Discharge Voltage: 11kV DC max

  • Peak Discharge Current: 1.1A for 100ms

  • Bleeder Resistance: 10kΩ

  • Discharge Capacitance: 10μF

  • Leakage Current at 35kV AC: <50μA

  • Discharge Energy: 3675J

Physical & Environmental Details

  • Cooling: Neutral

  • Total Size: 32mm × 750mm

  • Weight: 2.2kg (Net)

  • Safety Compliance: IEC 61230

  • EMC Compliance: Not Applicable

  • Operating Temperature: -5°C to 70°C

bottom of page